| Sl. No. |
TEST |
INFORMATION PROVIDED BY TESTS |
1 |
Interfacial Tension |
Indicates the presence of sludge and excessive polar contaminants from the cellulosic materials. |
2 |
Neutralization Number |
Indicates the acid contents in the oil. |
3 |
Moisture Content |
Indicates the total dissolved water in the oil. |
4 |
Flash Point |
Indicates the presence of some of the lower hydro -carbons. |
5 |
Sludge |
Indicates deposition of fibrous particles, dust, contaminants etc. |
6 |
Dielectric Dissipation Factor |
Indicates the contents of contaminants like soluble varnish, resins and other polar contaminants. Ageing of Oil. |
7 |
Resistivity |
8 |
Dielectric Strength |
Conductive contaminants present in the oil such as metallic cuttings or free water. |
9 |
Kinematic Viscosity |
Indicates that heat removal efficiency of oil. |
10 |
Pour Point |
Indicates freezing point of oil. |
11 |
Density |
Indicates heat dissipation characteristics. |
12 |
Dissolved Gas Analysis
- Methane
- Ethane
- Ethylene
- Acetylene
- Oxygen
- Nitrogen
- Carbon Dioxide
- Carbon Monoxide
- Hydrogen
- Total Gas Content
|
Laboratory tests revealing ppm of combustible gas.
It is powerful diagnostic preventive maintenance technique for monitoring internal condition of the transformer. |
13 |
Furan Analysis |
Indicates deterioration of paper insulation. |